SCR LIGHTING CONTROLLERS

CW-6161 Magnetic Control Relay
Single pole, 20 Amp
High In-Rush Duty


TECHNOLOGY

The CW-6161 is a magnetic type relay.

When it receives a momentary polarized pulse from a two-wire relay control system it provides a permanent On/Off control of lighting and other electrical loads. This status remains until the coil is re-magnetized.

 

 


Applications

  • On/Off control of lighting and other electrical loads
  • Energy management

Specifications

CW-6161 Magnetic Control Relay

Electrical Inputs (Low Voltage) ± 24 VDC, rectified half-waves, reverse polarity. Class II, 350 mA current
Electrical Outputs (Line Voltage) - Resistive load: 20 A, 347 VAC
- Inductive load: 20 A, 347 VAC
- Incandescent lamp: 2400 W, 120 VAC
- Fluorescent lamp: 20 A, 347 VAC
- H.I.D Lamp: 20 A, 347 VAC
- Motor: 1-1/2 HP at 220-277 VAC (general use).
- Motor: 1/2 HP at 120 VAC (tungsten)
Operation

- A positive pulse of 18 to 30 VDC opens the relay and disables the load (Off action)

- A negative pulse of -18 to –30 VDC closes the relay and enables the load (On action)

Test condition - Reliable contact opening mechanism for 30,000+ On/Off cycles on a full 20 A HID charge at 347 VAC (20 times/ minute switching cycle)

- In rush: Flawless operation up to 1,500 A for 20 milliseconds

- Ambient temperature: -30° C to 50° C
Override switch Manual On/Off operation lever (integral to the relay)
Status indicator Visual mechanical indicator of status (On or Off)
Wiring Two-wire for both pulse activation and state return command for automatic monitoring through a control panel indicator lamp or a host PC
Protection The CW-6161 is protected against permanent On position when keeping the switch in the On or Off positions.
Mounting Adapter mounted for easy removal. Mounts on WR-9910 Mounting Strap. Requires one space
Auxiliary contact (optional)

0.5 A, 125 VAC

Weight in lb (kg) 0.437 (0.198)
Certification Underwriters Laboratories (UL) listed