LINEAR STEP CONTROLLERS
CCE Series
Linear Step Controllers
Up to 32 stages

Virtual setting
Technology
On large kW custom heaters, a Cristal Controls’ electronic step power controller offers the full advantages of both the Cristal Controls’ SCR as well as step controller and can bring maximum energy savings.
In this system, normally recommended for precise temperature control on heaters drawing more than 100 Amps, one SCR heating stage, usually 25% larger than other heating stages, is proportionally controlled with Cristal Controls’ SCR.
The other heating stages are controlled by the electronic step controller. The SCR stage automatically fills the gaps between step controlled stages, thus providing fully proportional control over the entire heater kW range.
Advantages
- This scheme is far more economical than using SCR controllers to carry the entire heater load, but is entirely equivalent in operation
- Cristal Controls’s step controllers range from 2 to 32 steps
| Linear Step Controllers |
|
CCE-8 |
1 SCR modulating step + 8 ON/OFF Steps |
CCE-16
CCE-24
CCE-32 |
1 SCR modulating step + 16ON/OFF Steps (On metal Plate)
1-SCR modulating step+ 24ON/OFF Steps (On metal Plate)
1 SCR modulating step + 32 ON/OFF Steps (On metal Plate) |
Power supply |
24 Vac 100Ma Maximum |
Output steps
Control type |
1A @ 24 Vac, dry contact type
Cycle,sequence,LIFO,FIFO & Binary. |
Zero SCR |
Adjustable |
Span Input |
See complete documentation |
Input Signal |
10K, 0-135 Ohms, 0-10 V, 0-5V, 4@20 mA |
Operation Temperature |
-40F to +160F (-40C to +72C) |
Storage Temperature
Enclosure |
-40F to +160F (-40C to +72C)
Enclosure 35 mm Entrelec Din Rail |
Dimensions CCE-8 |
157 mm x 255 mm x 30 mm
4,0’’ x 6,5’’ X 1-3/16" |
Weight |
CCE-8 =159 Grams (5,6 oz) |
|
|